The chart below defines the test voltage and AC maximum use voltage for various classes of Electricials / Linemans gloves.
Chart of Insulation Ratings for Electrician's / Lineman's Gloves
.
CLASS NUMBER
TEST VOLTAGE
AC MAXIMUM USE VOLTAGE
00
2,500V
500V
0
5,000V
1,000V
1
10,000V
7,500V
2
20,000V
17,000V
3
30,000V
26,500V
4
40,000V
36,000V
Notes:
#1. These values are for educational purposes only.
#2. It is very important that, besides verifying the class of glove used for the
application are correct for the voltage exposure, the integrety of the glove insulation
must be verified before each use. See manufacturer's instructions for proper
applicaiton, testing and use of gloves.
#3. Whenever a manufacturer's recommendations differs from the above information,
utilize manufacturer's information.