Motor Circuit Designer Page
Determine the voltage of the application and then click on the highlighted text below to find the correct table for your application.
Select here for 200 VAC or 208 VAC motors
Select here for 230 VAC or 240 VAC motors
Select here for 460 VAC or 480 VAC motors
Select here for 575 VAC or 600 VAC motors
Notes:
Data For 200 (208) VAC 3 Phase NEMA Design B, C, or D Motors.
| HP | FLA | Wire | TD Fuse | TD Ckt Bkr | Conduit |
| 1/2 | 2.5 | 14 | 4 | 6 | 1/2 |
| 3/4 | 3.7 | 14 | 6 | 7 | 1/2 |
| 1 | 4.8 | 14 | 8 | 7 | 1/2 |
| 1.5 | 6.9 | 14 | 10 | 15 | 1/2 |
| 2 | 7.8 | 14 | 12 | 15 | 1/2 |
| 3 | 11 | 14 | 17.5 | 15 | 1/2 |
| 5 | 17.5 | 12 | 25 | 30 | 1/2 |
| 7.5 | 25.3 | 10 | 40 | 50 | 1/2 |
| 10 | 32.2 | 8 | 50 | 50 | 3/4 |
| 15 | 48.3 | 6 | 60 | 100 | 3/4 |
| 20 | 62.1 | 4 | 90 | 100 | 1 |
| 25 | 78.2 | 3 | 100 | 100 | 1 1/4 |
| 30 | 92 | 2 | 125 | 200 | 1 1/4 |
| 40 | 120 | 1/0 | 175 | 250 | 1 1/2 |
| 50 | 150 | 3/0 | 200 | 250 | 2 |
| 60 | 177 | 4/0 | 250 | 250 | 2 |
| 75 | 221 | 300MCM | 300 | 400 | 2 1/2 |
| 100 | 285 | 500MCM | 400 | 400 | 3 |
| 125 | 359 | (2)4/0 | 500 | 600 | (2)2 |
| 150 | 414 | (2)300MCM | 600 | 600 | (2)2 1/2 |
| 200 | 552 | (2)500MCM | 800 | 800 | (2)3 |
Data For 230 (240) VAC 3 Phase NEMA Design B, C, or D Motors.
| HP | FLA | Wire | TD Fuse | TD Ckt Bkr | Conduit |
| 1/2 | 2.2 | 14 | 3 | 6 | 1/2 |
| 3/4 | 3.2 | 14 | 5 | 7 | 1/2 |
| 1 | 4.2 | 14 | 6 | 7 | 1/2 |
| 1.5 | 6.0 | 14 | 7.5 | 15 | 1/2 |
| 2 | 6.8 | 14 | 10 | 15 | 1/2 |
| 3 | 9.6 | 14 | 15 | 15 | 1/2 |
| 5 | 15.2 | 12 | 20 | 15 | 1/2 |
| 7.5 | 22 | 10 | 30 | 30 | 1/2 |
| 10 | 28 | 8 | 40 | 50 | 3/4 |
| 15 | 42 | 6 | 60 | 100 | 3/4 |
| 20 | 54 | 4 | 60 | 100 | 1 |
| 25 | 68 | 4 | 100 | 100 | 1 |
| 30 | 80 | 3 | 100 | 100 | 1 1/4 |
| 40 | 104 | 1/0 | 150 | 250 | 1 1/2 |
| 50 | 130 | 2/0 | 200 | 250 | 2 |
| 60 | 154 | 3/0 | 200 | 250 | 2 |
| 75 | 192 | 4/0 | 300 | 250 | 2 1/2 |
| 100 | 248 | 500MCM | 350 | 400 | 3 |
| 125 | 312 | 500MCM | 400 | 600 | 3 |
| 150 | 360 | (2)4/0 | 500 | 600 | (2)2 |
| 200 | 480 | (2)300MCM | 600 | 600 | (2)2 1/2 |
Data For 460 (480) VAC 3 Phase NEMA Design B, C, or D Motors.
| HP | FLA | Wire | TD Fuse | TD Ckt Bkr | Conduit |
| 1/2 | 1.1 | 14 | 2 | 2 | 1/2 |
| 3/4 | 1.6 | 14 | 2 | 3 | 1/2 |
| 1 | 2.1 | 14 | 3 | 3 | 1/2 |
| 1.5 | 3.0 | 14 | 5 | 6 | 1/2 |
| 2 | 3.4 | 14 | 5 | 7 | 1/2 |
| 3 | 4.8 | 14 | 7.5 | 7 | 1/2 |
| 5 | 7.6 | 14 | 12 | 15 | 1/2 |
| 7.5 | 11 | 14 | 15 | 15 | 1/2 |
| 10 | 14 | 12 | 20 | 30 | 1/2 |
| 15 | 21 | 10 | 30 | 30 | 1/2 |
| 20 | 27 | 10 | 40 | 50 | 1/2 |
| 25 | 34 | 8 | 50 | 50 | 3/4 |
| 30 | 40 | 8 | 60 | 50 | 3/4 |
| 40 | 52 | 6 | 80 | 100 | 3/4 |
| 50 | 65 | 4 | 100 | 100 | 1 |
| 60 | 77 | 3 | 100 | 150 | 1 1/4 |
| 75 | 96 | 1/0 | 150 | 200 | 1 1/2 |
| 100 | 124 | 2/0 | 175 | 250 | 2 |
| 125 | 156 | 3/0 | 200 | 250 | 2 |
| 150 | 180 | 4/0 | 250 | 250 | 2 |
| 200 | 240 | 300MCM | 400 | 400 | 2 1/2 |
| 250 | 302 | 500MCM | 400 | 600 | 3 |
| 300 | 361 | (2)4/0 | 500 | 600 | (2)2 |
| 350 | 414 | (2)300MCM | 600 | 600 | (2)2 1/2 |
| 400 | 477 | (2)300MCM | 600 | 600 | (2)2 1/2 |
| 450 | 515 | (2)500MCM | 800 | 800 | (2)3 |
| 500 | 590 | (2)500MCM | 800 | 1200 | (2)3 |
Data For 575 (600) VAC 3 Phase NEMA Design B, C, or D Motors.
| HP | FLA | Wire | TD Fuse | TD Ckt Bkr | Conduit |
| 1/2 | 0.9 | 14 | 2 | 2 | 1/2 |
| 3/4 | 1.3 | 14 | 3 | 3 | 1/2 |
| 1 | 1.7 | 14 | 3 | 3 | 1/2 |
| 1.5 | 2.4 | 14 | 4 | 7 | 1/2 |
| 2 | 2.7 | 14 | 5 | 7 | 1/2 |
| 3 | 3.9 | 14 | 6 | 7 | 1/2 |
| 5 | 6.1 | 14 | 10 | 15 | 1/2 |
| 7.5 | 9 | 14 | 15 | 15 | 1/2 |
| 10 | 11 | 14 | 15 | 15 | 1/2 |
| 15 | 17 | 12 | 25 | 30 | 1/2 |
| 20 | 22 | 10 | 30 | 50 | 1/2 |
| 25 | 27 | 10 | 40 | 50 | 1/2 |
| 30 | 32 | 8 | 50 | 50 | 3/4 |
| 40 | 41 | 6 | 60 | 100 | 3/4 |
| 50 | 52 | 6 | 80 | 100 | 3/4 |
| 60 | 62 | 4 | 90 | 100 | 1 |
| 75 | 77 | 3 | 100 | 150 | 1 1/4 |
| 100 | 99 | 1/0 | 150 | 200 | 1 1/2 |
| 125 | 125 | 2/0 | 175 | 250 | 2 |
| 150 | 144 | 3/0 | 200 | 250 | 2 |
| 200 | 192 | 4/0 | 300 | 250 | 2 1/2 |
| 250 | 242 | 300MCM | 400 | 400 | 2 1/2 |
| 300 | 289 | 500MCM | 400 | 600 | 3 |
| 350 | 336 | (2)3/0 | 500 | 600 | (2)2 |
| 400 | 382 | (2)4/0 | 600 | 600 | (2)2 |
| 450 | 412 | (2)300MCM | 600 | 800 | (2)2 1/2 |
| 500 | 472 | (2)300MCM | 600 | 800 | (2)2 1/2 |
Notes:
#1. Motor Data based on 60Hz, NEMA Design B, C, or D, Standard Squirrel Cage Motors.
#2. Values for FLA are based on NEC Table 430-150. In actual application, please use nameplate FLA.
#3. Wire Size based on 75C wire types THW, THWN. in conduit allowing for 125% of FLA as required by NEC. Please refer to NEC for other applications
#4. Fuse size is based on NEC requirement of < 175% of FLA.
#5. Breaker size is based on NEC requirement of < 250% of FLA.
#6. Conduit size is based on maximum allowable fill amounts per NEC.
#7. Values based on NEC. It is user's sole responsibility to ensure actual motor circuit design conforms to all applicable national and local codes. These values are for educational purposes only. Due to the wide range of motor circuit applications, the author assumes no responsibility for the application of these values.